Fire safety is the largest single area of recorded non-compliance in the Paris MoU region, at 16.8% of deficiencies in 2025 . For a superintendent, the useful question is not whether fire fighting appliances on a ship are inspected, but which dates and records an inspector can check. This article sets out what falls due on fixed and portable appliances, what changed for foam in 2026, and how to reach a survey or port call ready.
Why Fire Fighting Appliances Draw So Much Attention
The Paris MoU detention rate reached 4.18% in 2025, up from 4.03% in 2024. Fire fighting equipment and appliances also appears among the top deficiency categories in the US Coast Guard’s 2024 data, as summarised by ABS. IMO’s maintenance guidelines set the expectation: fire protection systems and appliances should be in good order and readily available at all times. A lapsed date is as visible to an inspector as a faulty unit, and a serious deficiency can be detainable.
What Gets Inspected and When
IMO’s guidelines run from weekly to ten-yearly actions. Maker instructions, the flag and class can add to them, so treat this as a starting list.
| Appliance | What falls due | Basis |
| All fire protection systems | Weekly, monthly, quarterly, annual, two-year, five-year and ten-year actions | MSC.1/Circ.1432 |
| Fire pumps, hydrants and hoses | Annual flow test of fire pumps and test of hydrant valves. Sample pressure tests so every hose is tested within five years | MSC.1/Circ.1432 |
| Fire detection and alarm | Annual test | MSC.1/Circ.1432 |
| Fixed fire-fighting systems | CO2: Inspections fall due annually, every two years, every five years and every ten years. As per flag requirements, these inspections should be done by shore only. The biennial inspection i.e. the two-yearly inspection includes weight checks of the CO2 bottles. Control valves are inspected internally every five years. At the 10-year inspection, at least 10% of cylinders are inspected internally and hydrostatically tested. All cylinders are tested before the 20th anniversary and every ten years after. Foam: Annual flow test of the foam and water supply pumps. Concentrate samples go for periodic laboratory control tests, the first three years after supply, except for non-alcohol-resistant foam. Dry powder: Annual inspection, with powder agitation and moisture content testing. Containers are hydrostatically tested to the requirements in MSC.1/Circ.1432. Water mist: Annual inspection and function test to maker instructions and MSC.1/Circ.1432. | MSC.1/Circ.1432 MSC.1/Circ.1318/Rev.1 |
| Portable extinguishers | Examined annually by a competent person. Hydraulic test at intervals not exceeding ten years | Res. A.951(23); MSC.1/Circ.847 |
Foam: PFOS Is Now a Survey Item
From 1 January 2026, SOLAS Chapter II-2 prohibits using or storing fire-extinguishing media, including foam, that contains PFOS above 10 mg/kg. Ships built before that date must comply by the first scheduled survey on or after 1 January 2026. The evidence is a maker’s declaration or a laboratory test report. Where foam must go, tanks and systems need cleaning, replacement media must be certified PFOS-free, and removed foam must be delivered to a shore reception facility. The ship’s IHM Part I should then be updated to reflect the removal.
Where Ships Lose Time
Most problems are gaps between the guidelines and the records, not failed equipment.
- Intervals sit in different places. Annual, five-yearly and ten-yearly items are tracked in separate lists, so one slips.
- Test dates go unchecked. The hydrostatic test date should be marked on each cylinder, and it is checked every year.
- Foam evidence is missing. A PFOS declaration or report is needed, alongside the periodical control tests on the foam itself.
- Records are not on board. Records of inspection, maintenance and tests should be kept and available.
Each gap is avoidable with one calendar and one set of records.
How Marine Mechanics Supports Testing and Certification
Marine Mechanics inspects, tests and certifies fixed and portable fire fighting appliances on ships to Flag, Class and maker requirements. The scope covers fixed CO2 systems (inspection, bottle level checks and hydrotesting), fixed foam systems (inspection and laboratory foam analysis), fixed dry powder systems (inspection, agitation and moisture content testing), water mist, galley and clean agent systems, portable and non-portable extinguishers (inspection, hydrotesting, refill and supply), and fire alarm and detection systems. For foam, the service includes certified laboratory testing, PFOS-free foam supply and documented disposal support.
Work is planned around survey windows and port calls, due dates are tracked before they lapse, and documentation is prepared for Class, Flag and Port State review. Approvals include Bureau Veritas, Lloyd’s Register, ABS, ClassNK and Korean Register, with 24/7 remote support in every time zone.
Three Quick Questions
How often must portable fire extinguishers on a ship be inspected?
Every year, by a competent person, with a hydraulic test at intervals not exceeding ten years.
What is different about fixed CO2 systems?
They follow their own guidelines, MSC.1/Circ.1318/Rev.1. Control valves are inspected internally every five years, and the hydrostatic test regime for cylinders was tightened.
When must PFOS foam leave an existing ship?
By the first scheduled survey on or after 1 January 2026, with a maker’s declaration or laboratory report as evidence.
Marine Mechanics is a technical engineering partner for the full vessel lifecycle. To plan fire fighting appliance testing and certification around your next survey, write to mmsafety@marinemechanics.biz or see our Safety (LSA/FFA) page.
Other References
The following are additional supporting sources for the references above.
Fixed CO2 systems